750ADM-H mk3 Current Injection System
Primary injection up to 750A
4V output*
16V 40A output for secondary injection
True RMS memory ammeter with single cycle capture
Multi-function timing system
Large back-lit liquid crystal display
Thermal and over-current protection
Automatic switch-off at end of test
Compact and portable
Automatic mains voltage selection*
T&R Test Equipment is a market leader in the field of current injection equipment. The range includes secondary injection units with 100A output capability up to 6000A primary injection systems. All have true RMS metering, a flexible timing system, and an easy to understand user interface.
The 750ADM-H mk3 is a compact, rugged primary current injection system with a 750A output capability. The 750ADM-H mk3 has a maximum no load output voltage of 5V. The unit is ideally suited to all low power primary injection tasks requiring up to 750A for short periods. Where higher currents and powers are required for primary injection, 11kVA and 20kVA primary injection systems are also available.
The PCU1-SP and CU-PS systems have separate control units, allowing a wide range of load conditions to be met by different loading units.
The unit has two outputs, allowing injection of currents as low as a few hundred milliamps and up to 750A. Voltages up to 16V are available on the 40A output, allowing higher impedance trips to be tested. Four true RMS metering ranges are provided, allowing the full scale of the meter and trip level to be set independently of the selected output. The metering has a capture time of less than 20ms, allowing the RMS of a single cycle to be accurately measured. Industry standard connectors are used on all inputs and outputs for convenience, reliability and safety.
The 750ADM-H mk3 is comprehensively protected by electronic overcurrent and thermal trips.
The timing system is very flexible without compromising ease of use, allowing trip times, reset times and reclose times to be quickly measured to a high degree of accuracy. Two contact inputs are provided, each of which may be trigged by a volt-free contact or a DC voltage. The contact inputs auto-sense for normally open or normally closed contacts.
The 750ADM-H mk3 can be used to test many devices including:
Circuit breakers
Primary injection of over-current relays
Auto-reclosers
MCB’s
CT ratio (with external meter for secondary current)